How to: fix your Englander pellet stove.

There are a few things that need to happen when you start your Englander pellet stove.When the stove is safe to operate, power is sent to the upper auger and pellet to feed through the system and the controller looks at a few sensors to make sure.These techniques can be used to solve the problem if there are no pellets coming down.

This is usually a simple and easy fix.There is an air hose behind the combustion blower.Follow this procedure if you are getting this error.

You need to bench test the shutdown switch if everything goes well.

There are three problems with a pressure switch.1.When the switch is closed, it doesn't have continuity.2.Once it has continuity, the switch doesn't stay closed.Poor or partial continuity is what the switch has.

The pressure switch can be used in a variety of ways.We are using it as a pressure switch to turn on or off a component.The air hose needs to be on the gray side of the switch in order to look for negative pressure to close and open contact.The air hose should be removed from the stove switch.To properly test the switch, you will need about 2 feet of air hose, a T connection for the hose to create a branch, and a magnehelic gauge or manometer.

The gray side of the switch has a hose on it.Attach one side of the hose to the needle and the other side on the gauge.

The leads of your DMM should be on the NO and COM terminals.The DMM sounds off when the air is drawn from the system.The gauge has your reading on it.It should be.17”If the switch can hold pressure, the DMM should stay off.The DMM should go silent once the pressure is released.Pick up the pressure switch and tip it back and forth as the DMM sounds off.The pressure should be held by it.The switch is good if all of this goes well.If you don't replace the switch.

It can be passed at the board.Follow the leads back to the board.The control board that leaves the factory has a jumper on the outer side wall.Remove the small black jumper from the tape and replace it with a new one.Unless you are there to monitor it, do not attempt the jump.There is a chance that a house fire could result from a churchyard failure.The sledgehammer should never be allowed to be used in an emergency because of the danger it poses.